DDC Programming Logic 3DDC Programming Logic 3 - DDC control logic blocks have practically an unlimited way of arranging the blocks for HVAC control. Below is an example of a line of logic blocks arranged for static pressure control of a VAV air handler supply fan using a variable frequency drive. This same arrangement could also be used for static pressure control using a bypass damper instead of a VFD.

HVAC Control DDC Programming Logic Block Arrangements

The input and output logic blocks, where the analog input and the analog output, are hard-wired to control devices. The input logic block, in this case, is hard-wired to a static pressure transducer which is placed in the ductwork and reads static pressure. The analog output in this control logic arrangement is hard-wired to a variable frequency drive and sends the appropriate signal to the VFD depending on what the program calls for the output.

Secondary inputs are required in the program and are linked via the program. The secondary input requirement for this program is the fan status input which is on a completely different line (not shown). The fan status input is hard wired to a CT which is at the supply fan and reads either a 0 or 1. 0 being off and 1 being on and this depends on the contacts on the CT and whether they are closed or open.

DDC Programming Logic 3 - Understanding the Program Configurations & Logic

There are many other configurations on the board and in the program that a trained DDC Start-up Technician will be familiar with and set prior to energizing the DDC controller for the first time. There are jumper settings at the DDC controller and often times at the devices themselves.

Variable Frequency Drives also have jumper settings and a program array which must be configured to be compatible with the DDC control signal. There are also parameters inside the drive that must be matched up to the motor which includes voltage, amperage, and service factor information.

These settings depend on the VFD manufacturer and their requirements for settings. All of these settings and parameter changes need the attention of a qualified DDC Start-up Technician or Engineer before any DDC Controlled equipment is put into service. Additional a qualified testing and balancing company should balance the entire DDC system and HVAC systems before the system is released to the owner for use.

DDC Programming Logic 3 - Program Configuration

Each block in most programs is configurable by either navigating to a separate page or by clicking on the block. Clicking on the logic block will give you a pop-up window where additional parameters including physical input/output assignments can be made.

It is important when assigning these inputs and outputs that the parameters are verified and correct. A DDC start-up technician should set all the parameters necessary for the proper functioning of the program including tuning of the program to ensure efficient and proper operation of the HVAC equipment.

DDC Programming Logic 3 - The Control Logic

This arrangement of DDC control logic blocks is for static pressure control of a supply fan on a VAV air handler unit. Reading from left to right:

  • The analog input for the duct static pressure transducer is mounted in the ductwork in a strategic location according to control engineering parameters. This number feeds into the PID logic block along with the static pressure setpoint and the input from another line of logic for fan status which is a binary input.
  • The PID logic block processes the input it receives and makes a calculation for the necessary amount of output for the supply fan VFD. It sends this output to the next logic block.
  • The low limit analog signal logic block is the minimum percentage that the fan should run when there is low demand. If the setting on this logic block was 20% it would allow all analog signals over 20% but if the PID logic block sent it a 10% input the low limit analog signal block would only allow a minimum of a 20% output.
  • The digital switch will change according to fan status input. If the binary value of the fan status goes to zero then this switch will turn off giving all output to the right of this block a 0% signal.
  • The ramp-up analog block will limit the signal based on time so the fan doesn’t go to 100% in 1 second if the program calls for a 100% fan output signal to the next block.
  • This is the analog output signal to the variable frequency drive which controls the speed of the fan.

There are many other arrangements of DDC logic blocks that are used in DDC controls programming and this is just a sample of the arrangements of blocks and the unlimited control one can have by utilizing such an amazing system of HVAC DDC control.

DDC Control Logic Page 1 | DDC Control Logic Page 2

High Performance HVAC

DDC Programming Logic 3 - Your Resource for HVAC Technical Information