Trane Heat Pump Condenser
The average compressor in many residential air conditioner or heat pump condensing units are hermetically sealed compressors with the only visible working parts on the compressor are the electrical connections and the copper discharge and suction lines. This makes it difficult to repair any compressor once a diagnosis is made to the air conditioner or heat compressor. Troubleshooting air conditioning and heat pump compressors is not difficult once you understand the basics of the compressor. It doesn’t matter what kind of residential air conditioner or heat pump compressor you are working on as long as it is single phase for use in a residential heat pump or air conditioner. This article will cover the basics of troubleshooting a compressor when the circuit breaker trips continuously.
Different Air Conditioner or Heat Pump Compressors
Many residential heat pump or air conditioner compressors are black and a few are red depending on the manufacturer of the compressor. Trane is the only OEM in the USA that manufacturers their own compressors. This falls to American Standard because Trane and American Standard are owned by the same company. In any regard the color does not matter as all the components inside the compressor are the same. That is a scroll compressor is a scroll compressor. There are new scroll compressors out that have the ability to unload and other electronic scroll compressors that have the ability to fully modulate and this article does not address these newer scroll compressors. Scroll compressors and the scroll technology were initially owned by Copeland which is owned by Emerson Electric. There are also inverter duty compressors in some split system air conditioner and heat pumps manufactured by Nordyne and these compressors are different than the compressors we are talking about and that is the average air conditioner and heat pump compressor and require a different compressor troubleshooting analysis to technique than described here. So now that we know this and that it doesn’t matter what color the compressors are or who manufactured the compressor that every residential air conditioner or heat compressor is the same except the air conditioner or heat pump compressors mentioned above.
Troubleshooting the Air Conditioner Compressor – Compressor Basics
The Compressor Electrical Basics
Compressor Start & Run Windings Whether it is a scroll compressor or a reciprocating compressor (of which scrolls and reciprocating compressors make up the bulk of residential air conditioner or heat pump compressors in use today) there are two major components to the compressor. Each compressor has an electric motor and an assembly of mechanical components which are driven by the electric motor. The compressor electric motor has two separate windings inside for the average residential air conditioner or heat pump single phase compressors. The windings inside the compressor are the run winding and the start winding. When troubleshooting an air conditioner or heat pump compressor one should see three terminals on the outside of the compressor. These three electrical terminals are called or should be labeled in some manner – Common Terminal or C – Start Terminal or S – and the Run Terminal or R. Somewhere near these terminals there should some labels……….sometimes they say CSR and CSR stands for Common – Start – Run. These are the compressor basics. The other item in the electrical circuit for the compressor that you can troubleshoot with the compressor is the run capacitor. There are some compressors that also have start capacitors. The capacitors are external to the compressor and the run capacitor is wired in series with the run winding and start capacitor is wired in series with the start winding. The start capacitor will have a relay in the circuit as the start capacitor will only be used in the start circuit for a split second and then the relay, usually a potential relay and sometimes a current relay, will open the relay contacts pulling the start capacitor from the start circuit. The run capacitor remains in the run circuit for the duration of the compressor run time. For electrical compressor troubleshooting you will need an Ohm Meter, basic knowledge of electrical safety, and to know the aforementioned information. One word of caution………….capacitors hold a charge of electricity and you can be seriously injured or worse by coming into contact with a charged capacitor. When troubleshooting the electrical system of a compressor there are three different problems that can occur with the windings of the compressor.
Compressor Troubleshooting – Ohming the Windings
1. Shorted Windings – This is when the windings touch one another. This usually occurs because the insulation on each winding has dissolved allowing the copper windings to touch each other. Your Ohm Meter will likely read zero in this instance. The compressor is bad if you get this reading.
2. Open Winding – This occurs when a winding is open or broken. Your Ohm Meter will read infinity. If you get this reading the compressor is bad.
3. Grounded Winding – This nearly the same as an open winding except the winding is touching the casing of the compressor in some way. Your Ohm Meter reading will be zero from the terminal to the casing of the compressor. The best way to make this test is to touch one lead of the meter to the copper pipe going into the compressor (discharge or suction) and one of the CSR terminals.
If any of those conditions exist the circuit breaker for the condensing unit will trip when the compressor tries to start. If you perform this test and everything seems normal and the circuit breaker still trips you likely have a mechanical issue and we will address this next.
What is normal readings on the Ohm Meter you ask? A good example of normal reading would be resistance of say 7 Ohms on the start winding and 4 Ohms on the run winding. Your compressor may show a different measurement of Ohms but as long as you get resistance it is a good sign. If you measure between the run winding and the start winding you should get the sum of the other two readings. Example – C -S = 7 Ohms. C – R = 4 Ohms. S – R = 11 Ohms.
It is imperative that the compressor capacitors are functioning properly and are not bad. To properly check a capacitor to make sure it is good you need a special meter that reads microfarads. Some multi-meters have the ability to read microfarads but the reading from the meter should be plus or minus 10 percent of the rating on the capacitor.
The Compressor Mechanical Basics
Of the several types of compressors out on the market and that are installed in the average residential air conditioner and heat pump condenser we will only focus on the two types of basic compressors that make up approximately 95% of compressors installed in the average residential air conditioner or heat pump condenser or package unit. These two types of compressors are the scroll compressor and the reciprocating compressor with the scroll compressor overtaking the reciprocating compressor in volume of installations in the average residential air conditioner or heat pump condenser or package unit. To properly troubleshoot any compressor mechanically whether it is a reciprocating or a scroll you need to eliminate any electrical problems with the compressor. There is not much one can do if the mechanically or electrically broke except to replace the compressor but we must determine if there is a major uncorrectable problem with the compressor. One other test that can be done of the mechanical system will be an oil test but a special kit is required for this function. With the oil test kit a sample of the compressor oil is taken and then sent to a lab to determine that the oil contains all normal properties required of refrigerant oil. The compressor oil test kit can usually be purchased at an HVACR supply store. The oil test will only be necessary if you find the windings have shorted as this indicates a compressor burn out. If the compressor burned out it will need to be replaced. If you are replacing a burn out then the old oil will have to be flushed from the rest of the refrigeration circuit before putting the new compressor into service.
Compressor Troubleshooting – The Mechanical Components
After you have checked out all the electrical components and eliminated any problems with the electrical circuit and you continue to trip the circuit breaker for the condensing unit the next step is to try to eliminate any mechanical seizure of the compressor mechanical components. After I have checked the compressor electrical system and eliminated any problems with that I get an age old tool that every man loves. The hammer. This is true for reciprocating compressors but I cannot say I have found this works for any scroll compressors. If you have sued this compressor troubleshooting repair technique on a scroll and it worked for you please leave a comment below. We want to hear from you. I take a good hammer and hit the compressor a few good times and then restore power. Approximately fifty percent of the time the compressor comes to life and lives out a normal life. If that happens I always make sure there is a time delay in the compressor circuit as mechanical lock-ups are usually the result of short circuiting.
[rokbox title="HVAC Compressor Troubleshooting :: Compressor Windings for typical single phase compressor" size="561 350" thumb="http://highperformancehvac.com/hvac-refrigeration/wp-content/uploads/2011/07/compressor-windings-150x150.jpg"]http://highperformancehvac.com/hvac-refrigeration/wp-content/uploads/2011/07/compressor-windings.jpg[/rokbox]


troubleshooting a compressor thats offline/overload..this is embarrasing..im new on the job at an apartment complex here in St. Pete,FL.,tech school trained and 10 yrs exp,but im nervous and trying to be efficient,it gets down to ohming out the windings,no beep on my digital meter,bad compressor.rite? nope…..hmmm.. the darn OVERLOAD is IN the windings.I NEVER KNEW THIS!! and im embarrassed that i DIDNT know this (goodman 2 ton 13 seer, gsc…) i was my own worst enemy on that call.if i would have taken my time and hosed down the unit like we usually do first,i wouldnt be eating crow. so,when ya screw up you can still learn something. ( BUT WAIT theres more..it was under warranty and we get a bill today from the company that did the installs, for labor AND a new compressor,the tech told us tho’ after he was done that the compressor was STILL good.why did he replace a good compressor?because he was TOLD too? im not buyin that one.did my boss screw up or did he screw up?.—-to the EDITOR-i know this isnt a hammer to a scroll story but im exhausted and needed to tell the story.this website is the best,and im glad its here.thanks Layne W. -St. Pete, Fla