HVAC Control and Direct Digital Controls (DDC) Page Two
|
HVAC Control DDC Controls and Building Automation Systems Quickpage Jump Links
Technicial Aspects of DDCDDC/Building Automation Wiring Standards
DDC Page One: What it should do?
DDC HVAC COntrol Page Three: VAV Systems
DDC HVAC Control Page Four: DDC and Economizers
The (Field) Technical Aspects of DDC HVAC Control
A HVAC technician who knows nothing about DDC controls or HVAC control systems would wonder how these hvac control systems work. To understand DDC controls and hvac controls, one must understand basic electricity and circuits. Starting with a large commercial VAV air handling unit with three stages of DX cooling and add all the necessary hvac ddc control points. We have variable frequency drives (VFD's) on the return and supply blower fans. There is a mixed air damper which closes off the return and opens up to outside air for economizing and CO2 control. Static pressure control will be achieved with a duct pressure transducer and the DDC HVAC control program through the frequency drives and blower motors. DDC needs to monitor supply air temperature, mixed air temperature, and return air temperature along with outside air and outside humidity. We will also monitor the duct smoke detectors and a freezestat for safety reasons. This is the set-up and we need to make it work. We need to get a point count and set-up our inputs and outputs.
Digital or Binary Outputs
|
- Compressor Stage One
- Compressor Stage Two
- Compressor Stage Three
- Supply VFD Start/Stop
- Return VFD Start/Stop
Analog Outputs
- Supply VFD Speed
- Return VFD Speed
- Mixed Air Damper
Binary or Digital Inputs
- Smoke Detector
- Supply Fan Status
- Compressor Status (Only one compressor status for the first stage. We assume this compressor has two unloaders for the other two stages.)
- Freezestat
Analog Inputs
- Supply Air Temperature
- Return Air Temperature
- Mixed Air Temperature
- Duct Static pressure
- Outside Air (this point along with humidity can be networked across a comm trunk from a distant controller. If the network option is chosen these two points would be analog network inputs and hard wiring at this controller would be unnecessary.)
- Humidity
- Supply VFD Feedback
- Return VFD Feedback
|
|
Now, your asking yourself what analog, and binary, and digital inputs and outputs are?
- Digital or Binary Outputs - Digital and binary are the same. It simply means either on or off, 0 or 1. With DDC control these are either dry contacts or triacs. So with our compressor start/stop above we simply use DDC HVAC controls to energize a relay that starts or stops the compressor starter. These contacts are typically rated for 24 volts but may also use 120 volts depending on the manufacturer and the ratings of the dry contacts and/or triacs. Again with the VFD's we are simply energizing a relay that starts and/or stops the drive(s). These (digital or binary) contacts can also be used for Pulse Width Modulation (PWM) control.
- Analog Outputs - This is simply a modulating signal from DDC
to a particular device or piece of equipment. Our drives, depending on how they are set up in their local parameter programming will need a signal to tell it how fast to go. We want these drives to speed up and slow down according to what our static pressure set point is set at. There are three different typical signals we can send to these drives from DDC. These are a 4-20 Milliamp signal, a 0-10 volt DC signal, or a 2-10 volt DC signal. To keep it simple we'll set both drives and DDC up for a 0-10 volt DC signal. This is an output signal from DDC and an input signal to the drive. If we send 0 volts to the drive it will run at minimum, if we send 10 volts to the drive it will run at maximum. If we send it 5 volts it will run at half speed and so on and so forth depending on what the program calls for the output to send to the drive. These analog outputs can also be used to control SCR's for resistive heating loads.Variable Frequency Drives
- Binary or Digital Inputs - Again, binary and digital are the same. Some DDC manufacturers use binary and some use digital when they describe their inputs and outputs. This is where DDC monitors some dry contacts like the smoke detector. These contacts are normally closed and when the detector detects smoke the contacts open. DDC sees this and stops all blowers and sends alarms to the appropriate sources. (We don't necessarily rely on DDC to stop all the blowers. There should be a hard wired interlock that will stop all blowers if the smoke detector alarms.) The supply fan and compressor status inputs can come from either contacts on a CT or from aux contacts on the appropriate starters. Depending on how the program is set up, DDC simply wants to see an open or closed position from these sources.
- Analog Inputs - Again, an analog signal is a modulating signal. In this case, we have analog inputs. Input to DDC from a device or piece of equipment. Our temperature sensors are usually thermistors. Depending on the temperature, the resistance of a thermistor will change. DDC sends a small amount of current through the thermistor circuit. DDC will take the input current coming back through the thermistor circuit and translate it into a temperature. This is done in the program through tables in the database which are matched up to the rated resistance/ temperature of the thermistor. For the duct pressure transducer we are going to get a different type of signal back to DDC. We are going to power the transducer up with a separate 24 volts. According to different manufacturers, this 24 volts can be either AC or DC (read the instructions for the device). There may be optional settings on the transducer allowing you send (from the device) either a milliamp or a voltage signal to the input of DDC. For simplicities sake we'll select a 0-10 volt signal from the device to the input of DDC. There should be range settings on both the device and in the DDC program. These settings should be synchronized. Let us say for example that the range setting is 0-10 inches H2O. Therefore, with a 0-10 signal setting at the device and configured in DDC, when we get a 0 volt signal back from the device we have 0 inches H2O pressure. When we get 5 volts back from the device we have a pressure of 5 inches H2O and so on and so forth as the pressure changes so does the voltage coming from the device to DDC which will translate that into a pressure.
DDC/Building Automation Wiring Standards
A good DDC installation crew will use wiring installation standards to
|
Where consistency really counts in wiring standards is what color is wired where. An example of this is communication wiring. Communication wiring is generally 24 gauge 18-2 conductor shielded wire. The two conductors, generally one is white and one is black, should be terminated consistently throughout the project such as white is positive and black is negative or vice versa (terminations at the controllers on a network). It is super important that every technician responsible for terminating completely understands these wiring standards and what color is used as positive and what is used as negative. This will save lots of headaches and communication troubleshooting in the future.
DDC Related Links
DDC Controls Page 1: About DDC Controls and BAS | DDC Controls Page 3: DDC Controls & Variable Air Volume (VAV) Systems | DDC Controls Page 4: DDC Controls and Economizers | DDC Controls Page 5: Programming and DDC Logic | DDC Controls Programming Example | DDC Controls Technician Descriptions | Energy Recovery Wheels | Variable Speed Drives

Your Resource for HVAC Control Information

